PVC Insulated Power Cable(0.6/1.0KV)
额定电压0.6/1.0KV及以下聚氯乙烯绝缘电力电缆 
 
 
一、Product Standard
GBl2706—2002 standard equivalent to IEC502(1983)
二、Usage
This product is suitable for use in rated AC voltage(U0/u)0.6/1.0KV and below transmitting and distributing circuit
三、Property for Use
1.Allowed max.work temperature is 70℃,for short circuit(5s),conductor max.temperature is 160℃.
2.While laying cable,the environmental temperature should not be less than 0℃,for bend radius,should be not less than 10
    times of cable overall diameter.
    Note:Our factory can produce refractory 90℃and 120℃power cable.
四、Type and Name
 For cable type and name see table 1

3.For reference overall diameter and weight of cable,see Tables6.



4.  The20℃ 1km resistance converted from 0.6/1.0KV finished cable insulation resistance should be not less than 36.7MΩ·km.
5.  Under room temperature,finished cable can bear voltage test of AC 50HZ,3.5KV voltage test and will not be punctured for 5 minutes steady and sustained test.
6.  After being laid,cable should undergo DC voltage test.
We suggest the test be 4U0(U0 is the voltage fromthe conductor to earth.This product is 0.6KV)and time to be 5mins.

 